The water quantity, water temperature, water quality and water supply stability of the water source system are important factors affecting the operation effect of the water source heat pump system. When applying a water source heat pump, the principle requirements for the water source system are: sufficient water, moderate water temperature, appropriate water quality, and stable water supply. Specifically, the amount of water in the water source should be sufficient to meet the needs of the user's heating load or cooling load. If the amount of water is insufficient, the unit's heat and cooling capacity will be reduced, and the user's requirements will not be met.
The water temperature of the water source should be moderate, suitable for the operating conditions of the unit. For example, when the Tsinghua Tongfang GHP water source central air conditioning system is in the heating operation condition, the water source water temperature should be 12-22 °C; in the cooling operation condition, the water source water temperature should be 18-30 °C. The water quality of the water source should be suitable for the materials of the system unit, pipes and valves, so as not to cause serious corrosion damage. The water supply system has a high water supply guarantee rate, and the water supply function has long-term reliability, which can ensure long-term and stable operation of the water source heat pump central air-conditioning system.